WIKA PGS23.100 switchGAUGE
不銹鋼帶開關觸點耐震電接點壓力表
Bourdon tube pressure gauge with switch contacts
Models PGS23.1x0, stainless steel version
Bourdon tube pressure gauge model PGS23.100 with
switch contact model 831.1
Description
Wherever the process pressure has to be indicated locally,and, at the same time, circuits are to be made or broken, the model PGS23.1x0 switchGAUGE can be used.
Switch contacts (electrical alarm contacts) make or break an electric control circuit dependent upon the position of the instrument pointer. The switch contacts are adjustable over the full extent of the scale range (see DIN 16085), and are mounted predominantly below the dial, though also partly on top of the dial. The instrument pointer (actual value pointer) moves freely across the entire scale range, independent of the setting.
The set pointer can be adjusted using a removable adjustment key in the window.
Applications
Control and regulation of industrial processes
Monitoring of plants and switching of electric circuits
For gaseous and liquid aggressive media that are not highly viscous or crystallising, also in aggressive ambience
Process industry: Chemical, petrochemical, power plants,mining, on- and offshore, environmental technology, machine building and general plant construction
Special features
High reliability and long service life
Up to 4 switch contacts per instrument
Also available with liquid-filled case for high dynamic pressure loads or vibrations
Gauges with inductive contacts for use in hazardous areas with ATEX approval
Gauges with electronic contact for PLC applications
Gauges in safety version S3 (k)
Switch contacts consisting of several contacts can also be set to a single set point. Contact actuation is made when the actual value pointer travels beyond or below the desired set point.
The pressure gauge is manufactured in accordance with DIN 16085 and fulfils all requirements of the relevant standards (EN 837-1) and regulations for the on-site display of the working pressure of pressure vessels.
As switch contacts magnetic snap-action contacts, reed switches, inductive contacts - for requirements to ATEX - or electronic contacts for triggering a PLC are available.
For further information on the different switch contacts please see data sheet AC 08.01.
Standard version
Nominal size in mm
100, 160
Accuracy class
1.0
Scale ranges
0 … 0.6 to 0 … 1,600 bar
or all other equivalent vacuum or combined pressure and vacuum ranges
Pressure limitation
Steady: Full scale value
Fluctuating: 0.9 x full scale value
Short time: 1.3 x full scale value
Permissible temperature
Ambient: -20 ... +60 °C for gauges without liquid filling and gauges with silicone oil filling
Medium: +200 °C maximum without liquid filling
+100 °C maximum with liquid filling
Temperature effect
When the temperature of the measuring system deviates from the reference temperature (+20 °C):max. ±0.4 %/10 K of full scale value
Process connection
Stainless steel 316L,
lower mount (LM) or lower back mount (LBM)
G ½ B (male), 22 mm flats
Pressure element
Stainless steel 316L
< 100 bar: C-type
≥ 100 bar: Helical type
Movement
Stainless steel
Dial
Aluminium, white, black lettering
Pointer
Instrument pointer: Aluminium, black
Set pointer: red
Case
Stainless steel, scale ranges ≤ 0 ... 16 bar with compensating valve to vent case, with blow-out device in case back
With safety version: With solid baffle wall (Solidfront) and blow-out back, hermetically sealed, with internal pressure compensation
Window
Laminated safety glass
Bezel ring
Cam ring (bayonet type), stainless steel
Electrical connection
Terminal box
Ingress protection
IP 65 per EN 60529 / IEC 529
Switch contacts
Magnetic snap-action contact model 821
No control unit and no extra power supply required
Direct switching up to 250 V, 1 A
Up to 4 switch contacts per measuring instrument
Inductive contact model 831
Long service life due to non-contact sensor
Additional control unit required (model 904.xx)
With corresponding control unit suitable for use in zone 1 /21 (2 GD) hazardous areas
Low effect on the indication accuracy
Fail-safe switching at high switching rates
Insensitive to corrosion
Up to 3 switch contacts per measuring instrument
Electronic contact model 830 E
For direct triggering of a programmable logic controller(PLC)
2-wire system (option: 3-wire system)
Long service life due to non-contact sensor
Low effect on the indication accuracy
Fail-safe switching at high switching rates
Insensitive to corrosion
Up to 3 switch contacts per measuring instrument
Reed switch model 851
No control unit and no extra power supply required
Direct switching up to 250 V, 1 A
Also suitable for direct triggering of a programmable logic controller (PLC)
Free from wear as without contact
Up to two change-over contacts per measuring instrument
Switching function
The switching function of the switch is indicated by function index 1, 2 or 3.
Model 8xx.1: Contact makes (clockwise pointer motion)
Model 8xx.2: Contact breaks (clockwise pointer motion)
Models 821.3 and 851.3: Change over; one contact breaks and one contact makes simultaneously when pointer reaches set point
For further information please see data sheet AC 08.01, electrical switch contacts
Options
Other process connection
Sealings (model 910.17, see data sheet AC 09.08)
Liquid filling (observe: With safety version only lower mount)
Inductive contacts also in safety version (SN, S1N)
Dual scale
Panel mounting flange, polished stainless steel
Surface mounting flange, stainless steel
Surface mounting lugs on the back, stainless steel (safety version)
SIL2 approval (safety version)
Pressure switch per VdTÜV code of practice 100
Dimensions in mm
switchGAUGE model PGS23.100 with switch contact model 821, 831 or 830 E
switchGAUGE model PGS23.100 (safety version) with switch contact model 821, 831 or 830 E
switchGAUGE model PGS23.160 with switch contact model 821, 831 or 830 E
switchGAUGE model PGS23.160 (safety version) with switch contact model 821, 831 or 830 E
switchGAUGE model PGS23.100 with switch contact model 851.3 or 851.33
switchGAUGE Typ PGS23.100 (safety version) with switch contact model 851.3 or 851.33
switchGAUGE model PGS23.160 with switch contact model 851.3 or 851.33